![]() Where the room or space has a door leading directly to an exit or directly to the outside of the building.Buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.The requirements of 17.2.11.1.1 shall not apply to any of the following: Staff shall be drilled in the engagement and release of the locking means, from within and outside the room, as part of the emergency egress drills required by 17.7.2.The emergency action plan, required by 17.7.1, shall address the use of the locking and unlocking means from within and outside the room.Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80. ![]() The locking means shall not modify the door closer, panic hardware, or fire exit hardware.The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential.Locks, if remotely engaged, shall be unlockable from the classroom side of the door without the use of a key, tool, or special knowledge or effort.The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in.The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key, tool, or special knowledge or effort.The locking means shall be capable of being engaged without opening the door. ![]() Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all of the following conditions are met: